Remove failed hose bib and replaced with new. Checked for leaks, ran some water. Hose bib works as it should. Had to cut out an 8”x8” area of drywall to gain access, filled in hole with a white 8”x8” access panel.


David B.

David B. Job Checkin

Tune-up: Furnace Tune-up: AC Performed complete furnace tune-up per heating checklist. Checked heat exchanger, igniter, inducer motor, blower motor, venting, safety limits, and gas pressure. Removed and cleaned flame sensor and burners. Performed combustion analysis. Inspected blower compartment, flushed out drain trap, drain lines and fittings. - Service Tech: Michael - Furnace: Lennox (2016) - Age of Equipment: 8yrs old - Filter: 16x25x4 - recently replaced by owner - Check Igniter Ohm: 52.0ohm - Checked Inducer Amps: rated: .65 actual: .25/.44A - Blower Amps: rated: 7.7 actual: 2.0/3.1A - Checked Gas Pressure: 1.6/3.4” - Temperature Rise: rated: 50-80 actual: 66F - CO in Exhaust: 16ppm - Humid


David B.

David B. Job Checkin

Complete preventative maintenance - oil\filter, air filter, spark plugs, battery test and inspect, output voltage checked, inspect Fuel and electrical connections, confirm firmware, c\o cabinet, power simulation. Unit works as it should at this time.


David B.

David B. Job Checkin

Pull export from genset, reset fault, test operations.


David B.

David B. Job Checkin

Found gas valve wasn’t opening tapped and opened replaced gas valve and did furnace tuneup.

Found gas valve wasn’t opening tapped and opened replaced gas valve and did furnace tuneup.